The CPTH02 computing head associated with the local serial communication interface 232/TTL (ICL) CPT43006 allows to enable a refueling sequence and save the delivery data.
In this configuration, called AT12, it manages the connected peripherals on its own and transfers the data on the LAN network. The ICL interface is part of the metrological approval of the header (DM 30/10/2006 n ° 27252).
I would like more information or a quote
-
- Power supply: 230 VAC +10% -15% - 50/60 Hz (130 VAC +10% -15% - 50/60 Hz on request)
- Consumption with backlit LED system: 30 VA + load (max 100 VA)
- Operating temperature (OIML R117-1): -25°C ÷ +55°C
- Storage temperature: -40°C ÷ +85°C
- Measurement unit resolution: Centilitres
- Motor relay control output: 24 VDC 0,5 mA
- Predetermination solenoid valve output: 24 VDC 0,5 A (modulated PWM)
- Red/green light output: 15 VDC 0,1 A
- Relay contact for pump and solenoid valve activation: 24 VAC 1 A (optional)
- Pulse emitter input: 2 channels
- Predetermination (optional): Volume by keyboard or Host
- Low level input: Low level contact or connection to tank level systems
- Spare contact input: Programmable according to the type of dispenser
- Local serial connection: RS232/RS485 One-Wire
- Delivery data viewing: 1 display LCD backlit LED 6 digits hight 25 mm
- System data viewing: 1 display LCD 20 characters X 2 lines
- User keyboard: In vandal-proof 16-key metal
-